What one unit from your diesel generator really costs: a self-test

Writer: Vaultus
Vaultus
17 hours ago
6 min read

Updated 17 November 2026: added a monthly cost per unit sign-up.


At a business site whose generator runs most days, one unit of diesel power usually costs ₹32 to ₹46 once fuel, upkeep and the service contract are counted, against ₹8.5 to ₹9.5 for a grid unit (our calculation, across our example sites). Few sites know their own figure. This self-test works it out from records you already keep, then tells you plainly to keep your generator or how much your diesel could pay a year towards backup. It is just below; three worked examples follow.



The Storage Brief, guide, 17 November 2026


Why this number is missing

Finance sees a diesel bill; maintenance sees hours on a meter. Neither sees the cost of one unit. GRAP Stage I was invoked across Delhi-NCR on 21 October 2026.


What you need

  • Diesel invoices for 12 months, and tank stock at the start and end.

  • The DG logbook: running hours, and kW or kWh readings if you have them.

  • One electricity bill. Your grid rate is the bill amount ÷ units billed.

  • The nameplate (kVA, year) and your service contract.


If the logbook has gaps, use matching months for litres and hours and scale to 12.


The five steps

  1. Litres burnt. Litres invoiced, less any rise in tank stock.

  2. Units made, by route:

    • Energy meter: units on the DG meter over the same 12 months. Best.

    • Logbook: running hours x average kW during cuts, read from the DG panel.

    • Invoices only: load is worked out from litres per hour on a typical fuel curve. This route cannot catch missing diesel.

  3. Units per litre. Units ÷ litres.

  4. Cost per unit. Diesel price ÷ units per litre, plus running upkeep (oil, filters, repairs, overhaul reserve), plus fixed costs (service contract, retrofit, insurance) ÷ units. The Bureau of Energy Efficiency (BEE) guide cites makers' typical 3,200 running hours between overhauls for a high-speed engine.

  5. Compare. Set it next to your grid rate. A battery avoids only fuel and running upkeep; the service contract stays while the generator stays as backup.


Check the records first

  • Litres per hour the set cannot burn. A 250 kVA set at full load burns about 59 litres an hour on our curve (our calculation: 250 x 0.8 kW x 0.294 litres a unit). A logbook showing 80 is wrong.

  • Units per litre that are too good. BEE's voluntary star label (sets up to 19 kW, tested at 75% load) gives 5 stars at 220 g/kWh or less, about 3.8 units a litre (our calculation: 835 g a litre assumed ÷ 220). Above that, suspect the meter or invoices.

  • Too much diesel for the load. Over 10% above a typical set at your load needs explaining: a low kW reading, unlogged hours, a worn engine, a leak or theft. A kW reading 25% too low alone gives a gap of about 18% (our calculation: 250 kVA set, 80 kW logged against 100 kW real). Dip the tank before and after a cut before blaming anyone.

  • A set under 30% load. BEE's guide says engine load "needs to be maintained above 50%". On our curve, a set at 25% load needs about 35% more diesel per unit than at 75% (our calculation: 3.25 ÷ 2.40 units a litre).

  • What good looks like. BEE's monitoring table shows 2.76 to 3.45 units a litre for sets loaded at 65% or more (our calculation: 1 ÷ 0.362 and 1 ÷ 0.290 litres a unit). Below 65% load our typical curve is a judgement (about 2.8 at 40% load, our calculation), and the self-test grades your set at your own load.


Three worked examples

1. A Noida factory that should get a quote (an example). A 250 kVA set carries 80 kW during cuts for 720 hours a year and burns 20,477 litres.


  • Units per litre: 2.81, normal for 40% load (our calculation: 57,600 units ÷ 20,477 litres).

  • Cost per unit: ₹38.1: fuel ₹33.8, running upkeep ₹2.1, fixed costs ₹2.2 (our calculation). That is 4.2 times a ₹9 grid unit.

  • A year: ₹22.0 lakh on the generator, ₹16.8 lakh more than the same units at the grid rate (our calculation). That is the price of backup, not a saving on offer: during a cut the grid is not there.

  • The ceiling: a battery could avoid ₹36.0 of each unit and costs ₹10.6 a unit to charge at 85% round trip. Covering every running hour, diesel could pay up to ₹14.6 lakh a year towards it (our calculation: 57,600 x (36.0 − 10.6)). A battery costing more a year cannot pay from diesel savings alone.

  • With a quote: at ₹12 lakh a year (an example, not a quote), it needs 16,819 litres a year replaced. The site has 20,477, so diesel covers it. At ₹16 lakh a year it needs 22,425 litres: close, but not covered (our calculation).


For this figure every month, use the box under your self-test result. On the 1st we send it at that month's diesel price; reply with last month's litres and units to make it your real number. Only you receive it. Reply STOP to end it.


2. A Faridabad factory with a fuel gap (an example). A 320 kVA set carries 120 kW for 900 hours, and invoices show 47,806 litres.


  • Units per litre: 2.26, against about 2.94 for a typical set at 47% load (our calculation: 1,08,000 units ÷ 47,806 litres).

  • The gap: a typical set would burn about 36,774 litres, leaving 11,032 litres a year unexplained, worth ₹10.5 lakh (our calculation: (47,806 − 36,774) x 95.20).

  • What to do: explain the gap first. Recheck the kW reading and the hours, then dip the tank before and after the next cut and check the top-up register against invoices. Judged on the litres the set should burn, the site is still well above the keep line, but missing diesel should never be the reason to buy a battery.


3. A Gurugram office that should keep its generator (an example). The same 250 kVA set, 80 kW, but only 50 hours a year and 1,422 litres.


  • Cost per unit: ₹67.2, the dearest of the three, because a ₹1.25 lakh service contract is spread over 4,000 units (an example; our calculation: ₹31.3 a unit).

  • The ceiling: diesel could pay only about ₹1 lakh a year towards a battery (our calculation: 4,000 x (36.0 − 10.6)).

  • Verdict: keep the generator. The dearest units are often at sites where a battery pays least.


The mistake that flatters a battery most

Counting hours a battery cannot reach. A set running 1,500 hours a year in 8-hour scheduled cuts gives a 3-hour battery only about 560 hours (an example; our calculation: 1,500 x 3 ÷ 8). Split your logbook by cut length before asking for quotes. For long cuts, see the battery and generator hybrid guide.


How the self-test gives its answer

Impossible readings get "check your records first". Under about 200 battery-reachable hours or 2,500 litres a year: keep your generator. Above that, it shows the most your diesel could pay a year towards backup; enter one written quote and it says whether diesel savings cover it, come close or fall short. It never quotes a battery price.


What to do this week

  1. Add up 12 months of diesel invoices and copy running hours and any kW or kWh readings from the logbook.

  2. Run the self-test at the top of this page for each set. Take the cost per unit and diesel ceiling to your finance head.

  3. If it flags a fuel gap, ask your service contractor for a two-hour fuel trial at your usual load.


Questions people ask

Q: How do I calculate diesel generator cost per unit? A: Divide units made by litres burnt, divide the diesel price by that, then add upkeep and fixed costs per unit. At ₹95.20 a litre and 2.81 units a litre, fuel alone is ₹33.8 a unit (our calculation).


Q: Rerun the payback with our actual generator hours. What else do you need? A: Litres invoiced over the same months, the load during cuts, and how long each cut lasted. Hours only turn into rupees through those three.


Sources


Keep reading


Vaultus puts business batteries on a monthly plan. The battery maker installs and maintains the system, the site pays monthly, and the contract sets how much backup it gets. Send your last 12 months of electricity bills and diesel records to contact@vaultus.io, or run your own numbers with the site calculator.